Permit: T07EL01913
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
401 N CAMINO SANTIAGO
Address NEW:
401 N CAMINO SANTIAGO
Apply Date:
10/26/2007
Applicant:
AGUIRRE JON K & ELSA C CP/RS
Description:
UPGRADE:ELECTRIC TO 200 AMP
Outstanding Activity Conditions
Permit Number - T07EL01913
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/26/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL01913
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/26/2007 | ELECTRIC - SERVICE UPGRADE | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE CONDUCTORS TO HAVE PROPER MINIMUM CLEARANCE TO GRADE NEC 230.24, 230.36 2) NEED MINIMUM 24" OUT OF WEATHERHEAD ON A & B PHASE CONDUCTORS PER TEP 3) IDENTIFY NEUTRAL AS IT LEAVES WEATHERHEAD NEC 200.6 4) GROUND RODS TO BE 6' APART MINIMUM AND DRIVEN FLUSH NEC 250.53 5) BOND ALL METAL WATER AND GAS PIPING TO SERVICE AND SECURE TO STRUCTURE OR BURY NEC 250.104 6) SECURE SERVICE BETTER-PLASTIC ANCHORS NO EFFECTIVE NEC 110.13 7) NEED ACCESS TO WHERE SPLICES ARE MADE |
| 04/03/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. MAJUTA |
| 09/29/2008 | PERMIT FINALED | LJACKSON | Approved |