Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
401 N CAMINO SANTIAGO
Apply Date:
10/26/2007
Applicant:
AGUIRRE JON K & ELSA C CP/RS
Description:
UPGRADE:ELECTRIC TO 200 AMP

Outstanding Activity Conditions

Permit Number - T07EL01913
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
10/26/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T07EL01913
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/26/2007 ELECTRIC - SERVICE UPGRADE CCLEMENS Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE CONDUCTORS TO HAVE PROPER MINIMUM CLEARANCE TO GRADE NEC 230.24, 230.36
2) NEED MINIMUM 24" OUT OF WEATHERHEAD ON A & B PHASE CONDUCTORS PER TEP
3) IDENTIFY NEUTRAL AS IT LEAVES WEATHERHEAD NEC 200.6
4) GROUND RODS TO BE 6' APART MINIMUM AND DRIVEN FLUSH NEC 250.53
5) BOND ALL METAL WATER AND GAS PIPING TO SERVICE AND SECURE TO STRUCTURE OR BURY NEC 250.104
6) SECURE SERVICE BETTER-PLASTIC ANCHORS NO EFFECTIVE NEC 110.13
7) NEED ACCESS TO WHERE SPLICES ARE MADE
04/03/2008 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. MAJUTA
09/29/2008 PERMIT FINALED LJACKSON Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW