Permit: T07EL01913

Parcel: 116141910

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/02/2008 ELECTRIC - SERVICE UPGRADE Approved CALL FOR FINAL WHEN SWITCH OVER COMPLETE
12/26/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE CONDUCTORS TO HAVE PROPER MINIMUM CLEARANCE TO GRADE NEC 230.24, 230.36
2) NEED MINIMUM 24" OUT OF WEATHERHEAD ON A & B PHASE CONDUCTORS PER TEP
3) IDENTIFY NEUTRAL AS IT LEAVES WEATHERHEAD NEC 200.6
4) GROUND RODS TO BE 6' APART MINIMUM AND DRIVEN FLUSH NEC 250.53
5) BOND ALL METAL WATER AND GAS PIPING TO SERVICE AND SECURE TO STRUCTURE OR BURY NEC 250.104
6) SECURE SERVICE BETTER-PLASTIC ANCHORS NO EFFECTIVE NEC 110.13
7) NEED ACCESS TO WHERE SPLICES ARE MADE