Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2008 | ELECTRIC - SERVICE UPGRADE | Approved | CALL FOR FINAL WHEN SWITCH OVER COMPLETE | |
| 12/26/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE CONDUCTORS TO HAVE PROPER MINIMUM CLEARANCE TO GRADE NEC 230.24, 230.36 2) NEED MINIMUM 24" OUT OF WEATHERHEAD ON A & B PHASE CONDUCTORS PER TEP 3) IDENTIFY NEUTRAL AS IT LEAVES WEATHERHEAD NEC 200.6 4) GROUND RODS TO BE 6' APART MINIMUM AND DRIVEN FLUSH NEC 250.53 5) BOND ALL METAL WATER AND GAS PIPING TO SERVICE AND SECURE TO STRUCTURE OR BURY NEC 250.104 6) SECURE SERVICE BETTER-PLASTIC ANCHORS NO EFFECTIVE NEC 110.13 7) NEED ACCESS TO WHERE SPLICES ARE MADE |