Permit: T07EL01760
Permit Details
Apply Date:
10/01/2007
Applicant:
ZAKARI MAMATOU
Description:
ELECTRIC:UPGRADE
Permit Reviews
Permit Number - T07EL01760
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/01/2007 | ELECTRICAL | 10/01/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL01760
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/01/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01760
Permite Description: ELECTRIC:UPGRADE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* 1) GROUND RODS TO BE MINIMUM 6' APART 2) REMOVE PAINT AT GROUND CLAMP CONNECTION AT GAS PIPE 3) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE 4) INSTALL ROOF JACK |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01760
Permit Description: ELECTRIC:UPGRADE
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |