Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07EL01760

Parcel: 131100900


Addresses:

5501 E 25TH ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/23/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) GROUND RODS TO BE MINIMUM 6' APART
2) REMOVE PAINT AT GROUND CLAMP CONNECTION AT GAS PIPE
3) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE
4) INSTALL ROOF JACK
10/22/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*