Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) GROUND RODS TO BE MINIMUM 6' APART 2) REMOVE PAINT AT GROUND CLAMP CONNECTION AT GAS PIPE 3) RECALL AFTER TEP TIE IN AND SWING OVER COMPLETE 4) INSTALL ROOF JACK |
|
| 10/22/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |