Permit: T07EL01740
Permit Details
Apply Date:
09/26/2007
Applicant:
CLINTON JON
Description:
200 AMP SERVICE UPGRADE
Contractors:
- JOHNNY S ELECTRICAL SERVICE L L C
Outstanding Activity Conditions
Permit Number - T07EL01740
Permit Status: Expired
Permit Description: 200 AMP SERVICE UPGRADE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/26/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01740
Permit Description: 200 AMP SERVICE UPGRADE
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2007 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN WORKING CLEARANCES PER 110.26 2. PLEASE VERIFY LOCATION OF GROUND RODS 3. SECURE BOX TO WALL 4. LABEL ALL BREAKERS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER 5. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 6. SHEATHING OF CABLE TO BE 1/4" INTO ENCLOSURE 7. USE SPLICE CONNECTOR LISTED FOR COPPER TO ALUMINUM 8. NEED ANTI-OXIDE COMPOUND ON ALUMINUM CONDUCTORS |
02/01/2008 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
02/01/2008 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
02/04/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |