Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01740
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS 5 & 6 FROM 9/28/07 INSP. |
|
09/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN WORKING CLEARANCES PER 110.26 2. PLEASE VERIFY LOCATION OF GROUND RODS 3. SECURE BOX TO WALL 4. LABEL ALL BREAKERS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER 5. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 6. SHEATHING OF CABLE TO BE 1/4" INTO ENCLOSURE 7. USE SPLICE CONNECTOR LISTED FOR COPPER TO ALUMINUM 8. NEED ANTI-OXIDE COMPOUND ON ALUMINUM CONDUCTORS |