Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
931 S CARNEGIE DR
Apply Date:
09/14/2007
Applicant:
VILLALBA LUCIA
Description:
panel upgrade to 200amps
Contractors:
  • ENERGY SOURCE ELECTRIC INC *C

Outstanding Activity Conditions

Permit Number - T07EL01677
Permit Status: Expired
Permit Description: panel upgrade to 200amps
Total Outstanding Activity Conditions - 1
Date Name
09/14/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL01677
Permite Description: panel upgrade to 200amps
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE UPGRADE N/A Not Inspected
09/21/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING NEC 230.28
2. INSTALL GROUNDING ELECTRODES & GROUNDING ELECTRODE CONDUCTOR PER NEC 250 SECTION III
3. INSTALL PROPER SIZE LUG FOR GROUNDING CONDUCTOR TO SUB-PANEL
4. NEED TO BOND GAS & WATER PIPING -- NEC 250.104
5. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL
NEC 250.24
6. PROPERLY TERMINATE GROUNDING CONDUCTORS AT SUB-PANEL
7. SEAL OPENING IN BACK OF SERVICE PANEL WITH NON-COMBUSTIBLE MATERIAL
8. USE PROPER FITTING TO CONNECT 3/4" EMT TO SERVICE PANEL
9. SERVICE 3/4" EMT WITHIN 3' OF PANEL CONNECTION
10. CANNOT SEE INTO METER SECTION SERVICE ENERGIZED PRIOR TO APPROVALS

Documents

File Name Document Type  
None DOCUMENTS VIEW