Permit: T07EL01677
Permit Details
Apply Date:
09/14/2007
Applicant:
VILLALBA LUCIA
Description:
panel upgrade to 200amps
Contractors:
- ENERGY SOURCE ELECTRIC INC *C
Outstanding Activity Conditions
Permit Number - T07EL01677
Permit Status: Expired
Permit Description: panel upgrade to 200amps
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/14/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01677
Permite Description: panel upgrade to 200amps
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 09/21/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING NEC 230.28 2. INSTALL GROUNDING ELECTRODES & GROUNDING ELECTRODE CONDUCTOR PER NEC 250 SECTION III 3. INSTALL PROPER SIZE LUG FOR GROUNDING CONDUCTOR TO SUB-PANEL 4. NEED TO BOND GAS & WATER PIPING -- NEC 250.104 5. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL NEC 250.24 6. PROPERLY TERMINATE GROUNDING CONDUCTORS AT SUB-PANEL 7. SEAL OPENING IN BACK OF SERVICE PANEL WITH NON-COMBUSTIBLE MATERIAL 8. USE PROPER FITTING TO CONNECT 3/4" EMT TO SERVICE PANEL 9. SERVICE 3/4" EMT WITHIN 3' OF PANEL CONNECTION 10. CANNOT SEE INTO METER SECTION SERVICE ENERGIZED PRIOR TO APPROVALS |