Permit: T07EL01677

Parcel: 134250470


Addresses:

931 S CARNEGIE DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING NEC 230.28
2. INSTALL GROUNDING ELECTRODES & GROUNDING ELECTRODE CONDUCTOR PER NEC 250 SECTION III
3. INSTALL PROPER SIZE LUG FOR GROUNDING CONDUCTOR TO SUB-PANEL
4. NEED TO BOND GAS & WATER PIPING -- NEC 250.104
5. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL
NEC 250.24
6. PROPERLY TERMINATE GROUNDING CONDUCTORS AT SUB-PANEL
7. SEAL OPENING IN BACK OF SERVICE PANEL WITH NON-COMBUSTIBLE MATERIAL
8. USE PROPER FITTING TO CONNECT 3/4" EMT TO SERVICE PANEL
9. SERVICE 3/4" EMT WITHIN 3' OF PANEL CONNECTION
10. CANNOT SEE INTO METER SECTION SERVICE ENERGIZED PRIOR TO APPROVALS