Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING NEC 230.28 2. INSTALL GROUNDING ELECTRODES & GROUNDING ELECTRODE CONDUCTOR PER NEC 250 SECTION III 3. INSTALL PROPER SIZE LUG FOR GROUNDING CONDUCTOR TO SUB-PANEL 4. NEED TO BOND GAS & WATER PIPING -- NEC 250.104 5. GROUNDS & NEUTRALS TO BE SEPARATE AT SUB-PANEL NEC 250.24 6. PROPERLY TERMINATE GROUNDING CONDUCTORS AT SUB-PANEL 7. SEAL OPENING IN BACK OF SERVICE PANEL WITH NON-COMBUSTIBLE MATERIAL 8. USE PROPER FITTING TO CONNECT 3/4" EMT TO SERVICE PANEL 9. SERVICE 3/4" EMT WITHIN 3' OF PANEL CONNECTION 10. CANNOT SEE INTO METER SECTION SERVICE ENERGIZED PRIOR TO APPROVALS |