Permit: T07EL01560
Permit Details
Apply Date:
08/22/2007
Applicant:
MAJOR ELECTRIC INC,*C
Description:
EMERGENCY SERVICE REPAIR (APA)
Contractors:
- MAJOR ELECTRIC INC,*C
Outstanding Activity Conditions
Permit Number - T07EL01560
Permit Status: Expired
Permit Description: EMERGENCY SERVICE REPAIR (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/22/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01560
Permite Description: EMERGENCY SERVICE REPAIR (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | ELECTRIC - FINAL | N/A | Partial Approval | 1) ONE PHASE OF PARALLEL 500 MCM AL REPULLED, ONE EXISTING SET REUSED 2) EXISTING FEEDS WERE 500 MCM AL 3) NOTE: ALUM FEEDS 2 PARALLEL 500 MCM=620 APRI AND COPPER FEEDS 2 PARALLEL 500 MCM 760 A SEC/140 A DIFF AT CT CAN 4) SERVICE FEEDS 4-200 A DISCON=800 A AND 2 100 A DISCON/1000 A DISCON CAPACITY 5) LK TO RE-ENERGIZE GIVEN BASED ON EXISTING CONDITIONS-FINAL APPROVAL UPON VERIFICATION OF LOAD TO BE SUFFICIENTLY CARRED BY SERVICE LATERAL. NO APPROVED DRAWING REQUIRED-SUBMIT LETTER OF CAPABILITY. CHECK #8911 FOR INSPECTION FOR $108.00 RECEIVED FROM MAJOR ELECTRIC RICHARD ROBLES |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01560
Permit Description: EMERGENCY SERVICE REPAIR (APA)
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER R. MAJUTA |