Permit: T07EL01560

Parcel: 11518032F


Addresses:

1421 N 15TH AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/22/2007 ELECTRIC - FINAL Partial Approval 1) ONE PHASE OF PARALLEL 500 MCM AL REPULLED, ONE EXISTING SET REUSED
2) EXISTING FEEDS WERE 500 MCM AL
3) NOTE: ALUM FEEDS 2 PARALLEL 500 MCM=620 APRI AND COPPER FEEDS 2 PARALLEL 500 MCM 760 A SEC/140 A DIFF AT CT CAN
4) SERVICE FEEDS 4-200 A DISCON=800 A AND 2 100 A DISCON/1000 A DISCON CAPACITY
5) LK TO RE-ENERGIZE GIVEN BASED ON EXISTING CONDITIONS-FINAL APPROVAL UPON VERIFICATION OF LOAD TO BE SUFFICIENTLY CARRED BY SERVICE LATERAL. NO APPROVED DRAWING REQUIRED-SUBMIT LETTER OF CAPABILITY. CHECK #8911 FOR INSPECTION FOR $108.00 RECEIVED FROM MAJOR ELECTRIC RICHARD ROBLES