Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | ELECTRIC - FINAL | Partial Approval | 1) ONE PHASE OF PARALLEL 500 MCM AL REPULLED, ONE EXISTING SET REUSED 2) EXISTING FEEDS WERE 500 MCM AL 3) NOTE: ALUM FEEDS 2 PARALLEL 500 MCM=620 APRI AND COPPER FEEDS 2 PARALLEL 500 MCM 760 A SEC/140 A DIFF AT CT CAN 4) SERVICE FEEDS 4-200 A DISCON=800 A AND 2 100 A DISCON/1000 A DISCON CAPACITY 5) LK TO RE-ENERGIZE GIVEN BASED ON EXISTING CONDITIONS-FINAL APPROVAL UPON VERIFICATION OF LOAD TO BE SUFFICIENTLY CARRED BY SERVICE LATERAL. NO APPROVED DRAWING REQUIRED-SUBMIT LETTER OF CAPABILITY. CHECK #8911 FOR INSPECTION FOR $108.00 RECEIVED FROM MAJOR ELECTRIC RICHARD ROBLES |