Permit: T07EL01313
Permit Details
Apply Date:
07/16/2007
Applicant:
TANNER ACKEN
Description:
RELOCATE:ELECTRIC LINES
Contractors:
- CRYSTAL GENERAL CONTRACTORS L L C
Permit Reviews
Permit Number - T07EL01313
Permit Status: Expired
Permit Description: RELOCATE:ELECTRIC LINES
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/16/2007 | ELECTRICAL | 07/16/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL01313
Permit Status: Expired
Permit Description: RELOCATE:ELECTRIC LINES
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/16/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01313
Permite Description: RELOCATE:ELECTRIC LINES
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 09/10/2007 | ELECTRIC - SERVICE RELOCATION | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 09/10/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL NEW BRANCH CKT WIRING TO BE PERMITTED & INSPECTED 2. IDENTIFY SERVICE DISCONNECT AS A "SERVICE DISCONNECT" - NEC 230.70B 3. BOND WATER PIPE - NEC 250.104 4. REATTACH GROUNDING FOR TELEPHONE & CATV 5. RACEWAYS ENTERING TOP OF 3R ENCLOSURE TO BE MADE RAINTITE VIA SEALING LOCKNUT OR MYERS TYPE HUB NEC 110 |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01313
Permit Description: RELOCATE:ELECTRIC LINES
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* |
| 08/02/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |