Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL NEW BRANCH CKT WIRING TO BE PERMITTED & INSPECTED 2. IDENTIFY SERVICE DISCONNECT AS A "SERVICE DISCONNECT" - NEC 230.70B 3. BOND WATER PIPE - NEC 250.104 4. REATTACH GROUNDING FOR TELEPHONE & CATV 5. RACEWAYS ENTERING TOP OF 3R ENCLOSURE TO BE MADE RAINTITE VIA SEALING LOCKNUT OR MYERS TYPE HUB NEC 110 |
|
| 08/01/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |