Permit: T07EL01262
Permit Details
Apply Date:
07/06/2007
Applicant:
BLIZZARD BOB
Description:
upgrade to 200 amp electrical service
Contractors:
- ELECTRICAL WIZARD
Outstanding Activity Conditions
Permit Number - T07EL01262
Permit Status: Expired
Permit Description: upgrade to 200 amp electrical service
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/06/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01262
Permite Description: upgrade to 200 amp electrical service
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01262
Permit Description: upgrade to 200 amp electrical service
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* 1) CALL FOR FINAL ONCE SWITCHED OVER 2) 205 NCE 250-104 B GIVES THE METHODS APPROVED FOR BONDING GAS LINES, 1 TO NEUTRAL OF SERVICE, 2 TO GROUND COMING UP FROM RODS, 3 TO RODS THEMSELVES, 4 OR WHERE EQUIPMENT GROUND FOR THE CIRCUIT WHICH MAY BE THE ONE TO ENERGIZE THE GAS PIPING-CAN BE USED AS BONDING JUMPER 3) YOU NEED TO USE ONE OF ABOVE SEE CODE SECTION 4) WILL CLEAR FOR SERVICE SWITCH OVER CALL FOR FINAL |
| 07/18/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. MAJUTA |