Permit: T07EL01141
Permit Details
Apply Date:
06/14/2007
Applicant:
SUBA KIM
Description:
service upgrade
Contractors:
- JUST A LITTLE TILE INC
Outstanding Activity Conditions
Permit Number - T07EL01141
Permit Status: Expired
Permit Description: service upgrade
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/14/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL01141
Permite Description: service upgrade
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT AND MINERALLAC STRAPS - NEC 230.28 2. GROUND RODS TO BE MIN. 6' APART - NEC 250.53 & 250.56 3. INSTALL PROTECTIVE BUSHING AROUND SUB-PANEL FEED THROUGH BACK OF JUNCTION BOX AND SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL -- NEC 300 4. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO JUNCTION BOX AT RIGHT OF DOOR - NEC 250.148 5. INSTALL PROTECTIVE BUSHING AROUND BRANCH CIRCUIT CONDUCTORS AT JUNCTION BOX AT RIGHT OF BACK DOOR AND SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL01141
Permit Description: service upgrade
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 08/13/2007 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 02/05/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. JIROUDEK |