Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
MULTI FAMILY OTHER
Apply Date:
05/22/2007
Applicant:
SHINGLETON, GERALD LEE
Description:
ELEC UPGRADE 400AMPS
Architects:
  • SHINGLETON, GERALD LEE
Contractors:
  • MULTIFAMILY SERVICES BUILDING INC

Permit Reviews

Permit Number - T07EL00973
Permit Status: Expired
Permit Description: ELEC UPGRADE 400AMPS
Start Date Submittal Complete Date Status  
05/22/2007 ELECTRICAL 05/22/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL00973
Permit Status: Expired
Permit Description: ELEC UPGRADE 400AMPS
Total Outstanding Activity Conditions - 1
Date Name
05/22/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL00973
Permite Description: ELEC UPGRADE 400AMPS
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
07/10/2007 ELECTRIC - INTERMEDIATE N/A Not ready for Inspection IVRS - Inspection :*
07/10/2007 ELECTRIC - SERVICE UPGRADE N/A Not ready for Inspection IVRS - Inspection :*
07/10/2007 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*
NOTES:
- NOTES ON APPROVED PLANS CALL OUT FOR 22K RATED BREAKERS IN APT. SUB-PANELS, ALSO CALLS FOR #1 COPPER FEEDERS - EXISTING IS #2 ALUM.
- VERIFY WITH TEP FOR LOAD & FEEDERS, AVAIL. TO EXISTING SES AT THESE BLD. ARE SUFFICIENT FOR NEW LOADS
- EXISTING SES, METER PACKS RATED 400 AMP. 240V

Documents

File Name Document Type  
None DOCUMENTS VIEW