Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00973
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOTES: - NOTES ON APPROVED PLANS CALL OUT FOR 22K RATED BREAKERS IN APT. SUB-PANELS, ALSO CALLS FOR #1 COPPER FEEDERS - EXISTING IS #2 ALUM. - VERIFY WITH TEP FOR LOAD & FEEDERS, AVAIL. TO EXISTING SES AT THESE BLD. ARE SUFFICIENT FOR NEW LOADS - EXISTING SES, METER PACKS RATED 400 AMP. 240V |