Permit: T07EL00973

Parcel: 13819029C

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00973

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
07/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NOTES:
- NOTES ON APPROVED PLANS CALL OUT FOR 22K RATED BREAKERS IN APT. SUB-PANELS, ALSO CALLS FOR #1 COPPER FEEDERS - EXISTING IS #2 ALUM.
- VERIFY WITH TEP FOR LOAD & FEEDERS, AVAIL. TO EXISTING SES AT THESE BLD. ARE SUFFICIENT FOR NEW LOADS
- EXISTING SES, METER PACKS RATED 400 AMP. 240V