Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07EL00810
Permit Details
Apply Date:
05/04/2007
Applicant:
JOHNSON CARLIER INC ,
Description:
RELOCATING POWER FOR BUILDING ONE
Contractors:
- JOHNSON CARLIER INC ,
Permit Reviews
Permit Number - T07EL00810
Permit Status: Closed
Permit Description: RELOCATING POWER FOR BUILDING ONE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/04/2007 | ELECTRICAL | 05/04/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL00810
Permit Status: Closed
Permit Description: RELOCATING POWER FOR BUILDING ONE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/04/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T07EL00810
Permit Description: RELOCATING POWER FOR BUILDING ONE
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2007 | ELECTRIC - SERVICE RELOCATION | RJIROUDE | Approved | IVRS - Inspection :* 1) INSTALL GRAND CONDUCTOR WITH FEEDERS TO GUTTER 2) INSTALL GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONTRACTOR 3) INSTALL CLASS T FUSES ON CHECK WITH ENGINEERS IF RK1 FUSES ARE OK 4) STRAP SERVICE RISERS |
06/14/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED FOR BLDG #1 PER R. JIROUDEK |