Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T07EL00810
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/29/2008 | ELECTRIC - SERVICE RELOCATION | Approved | ||
06/13/2007 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1) INSTALL GRAND CONDUCTOR WITH FEEDERS TO GUTTER 2) INSTALL GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONTRACTOR 3) INSTALL CLASS T FUSES ON CHECK WITH ENGINEERS IF RK1 FUSES ARE OK 4) STRAP SERVICE RISERS |
|
06/06/2007 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* 1. OK (2) 3" PVC CONDUITS FROM UTILITY JUNCTION BOX TO SES 2. OK 1" PVC TO REFEED PARKING LOT LIGHTS 3. INSTALL WARNING RIBBON PER NEC 300.5 |