Permit: T07EL00810

Parcel: 135084520


Addresses:

7150 E 22ND ST 01

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
02/29/2008 ELECTRIC - SERVICE RELOCATION Approved
06/13/2007 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
1) INSTALL GRAND CONDUCTOR WITH FEEDERS TO GUTTER
2) INSTALL GROUNDING ELECTRODES AND GROUNDING ELECTRODE CONTRACTOR
3) INSTALL CLASS T FUSES ON CHECK WITH ENGINEERS IF RK1 FUSES ARE OK
4) STRAP SERVICE RISERS
06/06/2007 ELECTRIC - SERVICE RELOCATION Partial Approval IVRS - Inspection :*
1. OK (2) 3" PVC CONDUITS FROM UTILITY JUNCTION
BOX TO SES
2. OK 1" PVC TO REFEED PARKING LOT LIGHTS
3. INSTALL WARNING RIBBON PER NEC 300.5