Permit: T07EL00790
Permit Details
Apply Date:
05/02/2007
Applicant:
AARMOR ELECTRIC
Description:
UPGRADE: 200 AMP
Contractors:
- AARMOR ELECTRIC
Permit Reviews
Permit Number - T07EL00790
Permit Status: Expired
Permit Description: UPGRADE: 200 AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/02/2007 | ELECTRICAL | 05/02/2007 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T07EL00790
Permit Status: Expired
Permit Description: UPGRADE: 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/02/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL00790
Permite Description: UPGRADE: 200 AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE A LISTED GUY KIT OR STIFF ARMS FOR MAST BRACE AND SECURE TO STRUCTURE (TRUSSES) EMT NOT ALLOWED NEC 230.28 2. IDENTIFY SERVICE NEUTRAL OUT OF WEATHERHEAD NOT JUST AT END - NEC 200.6 3. MOVE SERVICE LUGS TO OVERHEAD POSITION AS INDICATED ON DIRECTION STICKER IN METER SECTION - NEC 110.3 B 4. EQUIPMENT GROUND TO J-BOX UNDERSIZED - NEC 250.122 C 5. PROVIDE SEPARATE, PROPERLY SIZED NEUTRAL FOR DRYER -- NEC 220 6. PROPERLY IDENTIFY NEUTRAL(S) IN J-BOX - NEC 200.6 7. NEC AC CKT TO DISCONNECT? |