Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00790
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE A LISTED GUY KIT OR STIFF ARMS FOR MAST BRACE AND SECURE TO STRUCTURE (TRUSSES) EMT NOT ALLOWED NEC 230.28 2. IDENTIFY SERVICE NEUTRAL OUT OF WEATHERHEAD NOT JUST AT END - NEC 200.6 3. MOVE SERVICE LUGS TO OVERHEAD POSITION AS INDICATED ON DIRECTION STICKER IN METER SECTION - NEC 110.3 B 4. EQUIPMENT GROUND TO J-BOX UNDERSIZED - NEC 250.122 C 5. PROVIDE SEPARATE, PROPERLY SIZED NEUTRAL FOR DRYER -- NEC 220 6. PROPERLY IDENTIFY NEUTRAL(S) IN J-BOX - NEC 200.6 7. NEC AC CKT TO DISCONNECT? |