Permit: T07EL00666
Permit Details
Apply Date:
04/16/2007
Applicant:
HARO ARMANDO & NORMA A JT/RS
Description:
UPGRADE:ELECTRIC 200AMP
Permit Reviews
Permit Number - T07EL00666
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/16/2007 | ELECTRICAL | 04/16/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL00666
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/16/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL00666
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PERMIT FINALED | N/A | Not Inspected | ||
| 04/19/2007 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE LISTED BRACE OR GUY KIT FOR MAST -- NEC 230.28 2. BURY OR SECURE TO STRUCTURE GROUNDING ELECTRODE CONDUCTOR. 3. NEED METAL ADDRESS/UNIT # LABELS 4. HAVE MAX. 15 AMP. BREAKER FOR #12 COPPER CLAD CONDUCTOR. 5. PROPERLY GROUND INTERIOR J-BOX 6. USE INHIBITOR (OXIDATION) ON ALL ALUMINUM TERMINATIONS 7. BOND GAS PIPE 8. MAKE SURE WIRING IS NOT MIXED BETWEEN UNITS EACH ON ITS OWN METER. |
| 04/20/2007 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL00666
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR #1 & #2 PER C. CLEMENS |