Permit: T07EL00666

Parcel: 106011670

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/19/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
1. USE LISTED BRACE OR GUY KIT FOR MAST -- NEC 230.28
2. BURY OR SECURE TO STRUCTURE GROUNDING ELECTRODE CONDUCTOR.
3. NEED METAL ADDRESS/UNIT # LABELS
4. HAVE MAX. 15 AMP. BREAKER FOR #12 COPPER CLAD CONDUCTOR.
5. PROPERLY GROUND INTERIOR J-BOX
6. USE INHIBITOR (OXIDATION) ON ALL ALUMINUM TERMINATIONS
7. BOND GAS PIPE
8. MAKE SURE WIRING IS NOT MIXED BETWEEN UNITS EACH ON ITS OWN METER.