Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE LISTED BRACE OR GUY KIT FOR MAST -- NEC 230.28 2. BURY OR SECURE TO STRUCTURE GROUNDING ELECTRODE CONDUCTOR. 3. NEED METAL ADDRESS/UNIT # LABELS 4. HAVE MAX. 15 AMP. BREAKER FOR #12 COPPER CLAD CONDUCTOR. 5. PROPERLY GROUND INTERIOR J-BOX 6. USE INHIBITOR (OXIDATION) ON ALL ALUMINUM TERMINATIONS 7. BOND GAS PIPE 8. MAKE SURE WIRING IS NOT MIXED BETWEEN UNITS EACH ON ITS OWN METER. |