Permit: T07EL00329
Permit Details
Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address:
941 W CLEARWATER DR
Address NEW:
941 W CLEARWATER DR
Apply Date:
02/23/2007
Applicant:
CONZEMIUS JOSH
Description:
RECONNECT:ELECTRIC RESIDENCE
Outstanding Activity Conditions
Permit Number - T07EL00329
Permit Status: Withdrwn
Permit Description: RECONNECT:ELECTRIC RESIDENCE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/23/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T07EL00329
Permite Description: RECONNECT:ELECTRIC RESIDENCE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 02/27/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RESUPPORT CABLING UNDER ROOF OVERHANG ON WEST SIDE. 2. LOOSE RECEPT OVER KITCHEN COUNTER - RESUPPORT 3. INSTALL 20 AMP GROUNDED OUTLET (RECEPTACLE) FOR AC UNIT IN WALL - 15 AMP RECEPT. CAUSING HEAT DAMAGE TO AC UNIT CORD - BOTH UNITS EAST & WEST WALLS BE SURE TO RUN DEDICATED CIRCUITS TO PREVENT OVERHEATING. 4. INSTALL SMOKE DETECTORS IN BEDROOMS 5. CALL T.E.P TO REINSULATE CONDUCTORS AT POA |