Permit: T07EL00329

Parcel: 116212690


Addresses:

941 W CLEARWATER DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RESUPPORT CABLING UNDER ROOF OVERHANG ON WEST SIDE.
2. LOOSE RECEPT OVER KITCHEN COUNTER - RESUPPORT
3. INSTALL 20 AMP GROUNDED OUTLET (RECEPTACLE) FOR AC UNIT IN WALL - 15 AMP RECEPT. CAUSING HEAT DAMAGE TO AC UNIT CORD - BOTH UNITS EAST & WEST WALLS BE SURE TO RUN DEDICATED CIRCUITS TO PREVENT OVERHEATING.
4. INSTALL SMOKE DETECTORS IN BEDROOMS
5. CALL T.E.P TO REINSULATE CONDUCTORS AT POA