Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
1402 N CRAYCROFT RD
Apply Date:
02/21/2007
Applicant:
WERTH MARILYN M TR
Description:
INSTALL OUTDOOR LIGHTNING & ADD BREAKER BOX T07VL00010 WOP

Permit Reviews

Permit Number - T07EL00310
Permit Status: Expired
Permit Description: INSTALL OUTDOOR LIGHTNING & ADD BREAKER BOX T07VL00010 WOP
Start Date Submittal Complete Date Status  
02/21/2007 ELECTRICAL 02/21/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07EL00310
Permit Status: Expired
Permit Description: INSTALL OUTDOOR LIGHTNING & ADD BREAKER BOX T07VL00010 WOP
Total Outstanding Activity Conditions - 1
Date Name
02/21/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL00310
Permite Description: INSTALL OUTDOOR LIGHTNING & ADD BREAKER BOX T07VL00010 WOP
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/04/2007 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1. SEAL UNUSED OPENINGS IN PANEL
2. PROPERLY SEAT PVC CONDUITS INTO FITTINGS
3. USE APPROVED SPLICE CONNECTORS FOR GROUND CONDUCTOR & TERMINATION TO BE 3/4 OF A TURN UNDER SCREW.
4. USE BREAKER FOR AMPACITY OF CONDUCTORS
5. MISSING DEAD FRONT COVER
6. LABEL TIME CLOCK

Completed Inspections

Permit Status: Expired
Permit Number: T07EL00310
Permit Description: INSTALL OUTDOOR LIGHTNING & ADD BREAKER BOX T07VL00010 WOP
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/10/2007 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW