Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEAL UNUSED OPENINGS IN PANEL 2. PROPERLY SEAT PVC CONDUITS INTO FITTINGS 3. USE APPROVED SPLICE CONNECTORS FOR GROUND CONDUCTOR & TERMINATION TO BE 3/4 OF A TURN UNDER SCREW. 4. USE BREAKER FOR AMPACITY OF CONDUCTORS 5. MISSING DEAD FRONT COVER 6. LABEL TIME CLOCK |
|
| 05/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :$ |