Permit: T07EL00310

Parcel: 121063160


Addresses:

1402 N CRAYCROFT RD


Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL00310

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
06/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEAL UNUSED OPENINGS IN PANEL
2. PROPERLY SEAT PVC CONDUITS INTO FITTINGS
3. USE APPROVED SPLICE CONNECTORS FOR GROUND CONDUCTOR & TERMINATION TO BE 3/4 OF A TURN UNDER SCREW.
4. USE BREAKER FOR AMPACITY OF CONDUCTORS
5. MISSING DEAD FRONT COVER
6. LABEL TIME CLOCK
05/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :$