Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07EL00187
Permit Details
Apply Date:
02/01/2007
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
ELEC FOR FUEL TANK
Contractors:
- FAST FAB ERECTORS INC ,
Permit Reviews
Permit Number - T07EL00187
Permit Status: Final
Permit Description: ELEC FOR FUEL TANK
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/01/2007 | ELECTRICAL | 02/01/2007 | COMPLETED |
02/01/2007 | ELECTRICAL | 02/01/2007 | COMPLETED |
05/11/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 09/07/2007 | COMPLETED |
09/28/2007 | ELECTRICAL | 11/30/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL00187
Permit Status: Final
Permit Description: ELEC FOR FUEL TANK
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/01/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL00187
Permit Description: ELEC FOR FUEL TANK
Total Completed Inspections - 8
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2007 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* 1) INSTALL FUSES IN DISC. SW.'S 2) BOND BUSHINGS REQUIRED IN PANEL PER 501.30 NCE 3) OK TO POUR SEALANT IN SEAL OFFS 4) INSTALL SIGNS FOR EM STOP BUTTONS 514.11 NCE 5) PROVIDE LETTER FROM ENGINEER OF RECORD TO VERIFY COMPLIANCE WITH 514.11 AND 514.13 NEC |
12/21/2007 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
02/27/2008 | ELECTRIC - RECONNECT | DSANTACR | Approved | IVRS - Inspection :* |
02/27/2008 | ELECTRIC - TEMP POWER FOR TEST | DSANTACR | Approved | IVRS - Inspection :* |
02/27/2008 | ELECTRIC - TEMPORARY SERVICE | DSANTACR | Approved | IVRS - Inspection :* |
02/27/2008 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection :* |
02/27/2008 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
02/28/2008 | PERMIT FINALED | BFLORES | Approved |