Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED LETTER PER NOTE #5 |
|
| 01/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SEE NOTE #5 LAST INSP. |
|
| 12/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL FUSES IN DISC. SW.'S 2) BOND BUSHINGS REQUIRED IN PANEL PER 501.30 NCE 3) OK TO POUR SEALANT IN SEAL OFFS 4) INSTALL SIGNS FOR EM STOP BUTTONS 514.11 NCE 5) PROVIDE LETTER FROM ENGINEER OF RECORD TO VERIFY COMPLIANCE WITH 514.11 AND 514.13 NEC |