Permit: T07EL00140
Permit Details
Apply Date:
01/24/2007
Applicant:
MEHL SANDRA
Description:
Install 1 - 480v 3-phase meter base, 1 - 277/480v 3-phase 100amp panel board, 1- 277v control for north access road pole lights.
Contractors:
- MEHL ELECTRIC SERVICE INC,*C
Permit Reviews
Permit Number - T07EL00140
Permit Status: Expired
Permit Description: Install 1 - 480v 3-phase meter base, 1 -
277/480v 3-phase 100amp panel board,
1- 277v control for north access road
pole lights.
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/05/2007 | ELECTRICAL | 03/06/2007 | COMPLETED |
03/06/2007 | ELECTRICAL | 03/06/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07EL00140
Permit Status: Expired
Permit Description: Install 1 - 480v 3-phase meter base, 1 -
277/480v 3-phase 100amp panel board,
1- 277v control for north access road
pole lights.
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/24/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL00140
Permite Description: Install 1 - 480v 3-phase meter base, 1 -
277/480v 3-phase 100amp panel board,
1- 277v control for north access road
pole lights.
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* 1) 2" AND 1" PVC, 2 GROUND RODS, UG 2) PLEASE HAVE PLANS/PERMIT POSTED 3) RECALL INSPECTION |
05/14/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : 1. CONTRACTOR IS RECOGNIZED COMPONENT & MAY NOT BE SUITABLE FOR FIELD INSTALLATION OR USE AS LIGHTING CONTRACTOR. PLEASE VERIFY LISTING OF CONTACTOR. PER NEC 110.3 2. NEUTRAL CONDUCTORS (GROUNDED CONDUCTORS) #6 & SMALLER TO BE CONTINUOUSLY MARKED PER NEC 200.6 |
Completed Inspections
Permit Status: Expired
Permit Number: T07EL00140
Permit Description: Install 1 - 480v 3-phase meter base, 1 -
277/480v 3-phase 100amp panel board,
1- 277v control for north access road
pole lights.
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2007 | TEP CLEARANCE - AM | BFLORES | Approved | TEC PER R.JIROUDEK |