Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL00140
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. CONTRACTOR IS RECOGNIZED COMPONENT & MAY NOT BE SUITABLE FOR FIELD INSTALLATION OR USE AS LIGHTING CONTRACTOR. PLEASE VERIFY LISTING OF CONTACTOR. PER NEC 110.3 2. NEUTRAL CONDUCTORS (GROUNDED CONDUCTORS) #6 & SMALLER TO BE CONTINUOUSLY MARKED PER NEC 200.6 |
|
04/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECALL AFTER TEP TIE IN 2. CONNECTIONS IN PULL BOX TO BE WEATHERPROOF OK TO CLEAR TEC |
|
03/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLANS ARE NEEDED THIS IS A NEW SERVICE (480V) NOT AN UPGRADE. WILL NEED CITY STAMP 2. CONNECTIONS IN PULL BOX TO BE WEATHERPROOF |
|
02/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BONDING PER 250.92 NEEDED 2. PLEASE VERIFY BONDING PER 250.58 3. LABEL CIRCUIT DIRECTORY 4. NEED ELECTRICIAN PRESENT TO ACCESS PANEL 5. VERIFY SEALING OF ENTRANCES ABOVE CURRENT CARRING PARTS. 6. WHERE ARE PLANS AND PERMIT (#2 PREVIOUS INSP) |