Permit: T07EL00078
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
220 S CALLE DE LA AZUCENA
Address NEW:
220 S CALLE DE LA AZUCENA
Apply Date:
01/14/2007
Applicant:
WINKLE BRIAN
Description:
upgrade to 200 amps
Contractors:
- WINKLE ELECTRIC
Outstanding Activity Conditions
Permit Number - T07EL00078
Permit Status: Final
Permit Description: upgrade to 200 amps
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/14/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL00078
Permit Description: upgrade to 200 amps
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* 1) RECALL AFTER TEP SWING OVER AND REST OF WORK COMPLETE 2) INSPECTED 2 GROUND RODS OK |
| 03/16/2007 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* |
| 03/19/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED PER R. JIROUDEK |
| 08/31/2007 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE SELF-TAPPING SHEETMETAL SCREWS FOR CONNECTION OF GROUND BAR AT SUB-PANEL NEC 250.8 2. INSTALL PROTECTIVE BUSHING ON FEEDER TO SHOP SUB-PANEL NEC 352.46 3. PROVIDE ACCESS TO SHOP PANEL. NEEDS TO HAVE MAIN DISCONNECT AT SHOP FOR PANEL - NEC 225.31 & 225.32 4. NEED TO INSTALL GROUNDING ELECTRODES AT SHOP PER NEC 250.32 5. CANNOT VERIFY WATER PIPE BOND |
| 01/28/2008 | PERMIT FINALED | JWEATHER | Approved |