Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE SELF-TAPPING SHEETMETAL SCREWS FOR CONNECTION OF GROUND BAR AT SUB-PANEL NEC 250.8 2. INSTALL PROTECTIVE BUSHING ON FEEDER TO SHOP SUB-PANEL NEC 352.46 3. PROVIDE ACCESS TO SHOP PANEL. NEEDS TO HAVE MAIN DISCONNECT AT SHOP FOR PANEL - NEC 225.31 & 225.32 4. NEED TO INSTALL GROUNDING ELECTRODES AT SHOP PER NEC 250.32 5. CANNOT VERIFY WATER PIPE BOND |