Permit: T07EL00078

Parcel: 126161220

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE SELF-TAPPING SHEETMETAL SCREWS FOR CONNECTION OF GROUND BAR AT SUB-PANEL NEC 250.8
2. INSTALL PROTECTIVE BUSHING ON FEEDER TO SHOP SUB-PANEL NEC 352.46
3. PROVIDE ACCESS TO SHOP PANEL. NEEDS TO HAVE MAIN DISCONNECT AT SHOP FOR PANEL - NEC 225.31 & 225.32
4. NEED TO INSTALL GROUNDING ELECTRODES AT SHOP PER NEC 250.32
5. CANNOT VERIFY WATER PIPE BOND