609 N GENE PL
Address NEW:
609 N GENE PL
Apply Date:
01/11/2007
Applicant:
BAKER TODD
Description:
200 amp main service upgrade
Contractors:
  • BAKER S MOBILE AIRE INC ,

Outstanding Activity Conditions

Permit Number - T07EL00063
Permit Status: Expired
Permit Description: 200 amp main service upgrade
Total Outstanding Activity Conditions - 1
Date Name
01/11/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL00063
Permite Description: 200 amp main service upgrade
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
01/17/2007 ELECTRIC - UNDERGROUND N/A Not ready for Inspection IVRS - Inspection :*
01/17/2007 ELECTRIC - INTERMEDIATE N/A Not ready for Inspection IVRS - Inspection :*
01/17/2007 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1. PLEASE BOND A ROUND PLUMBING UNION TO MAINTAIN CONTINUITY.
2. RISE HARDWARE TO BE 1/4" MINIMUM
3. LABEL BREAKERS
4. GROUNDING ELECTRODE CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119
5. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES LABEL.
6. INSTALL ALL STRANDS UNDER TERMINAL LUG
7. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS.
8. PLEASE VERIFY PERMIT FOR NEW A/C UNIT
9. REDUCING WASHERS INSTALLED BACKWARDS.

Documents

File Name Document Type  
T07EL00063 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW