Permit: T07EL00063
Permit Details
Apply Date:
01/11/2007
Applicant:
BAKER TODD
Description:
200 amp main service upgrade
Contractors:
- BAKER S MOBILE AIRE INC ,
Outstanding Activity Conditions
Permit Number - T07EL00063
Permit Status: Expired
Permit Description: 200 amp main service upgrade
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/11/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07EL00063
Permite Description: 200 amp main service upgrade
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2007 | ELECTRIC - UNDERGROUND | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 01/17/2007 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 01/17/2007 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE BOND A ROUND PLUMBING UNION TO MAINTAIN CONTINUITY. 2. RISE HARDWARE TO BE 1/4" MINIMUM 3. LABEL BREAKERS 4. GROUNDING ELECTRODE CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119 5. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES LABEL. 6. INSTALL ALL STRANDS UNDER TERMINAL LUG 7. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS. 8. PLEASE VERIFY PERMIT FOR NEW A/C UNIT 9. REDUCING WASHERS INSTALLED BACKWARDS. |