Permit: T07EL00063

Parcel: 133351490


Addresses:

609 N GENE PL

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE BOND A ROUND PLUMBING UNION TO MAINTAIN CONTINUITY.
2. RISE HARDWARE TO BE 1/4" MINIMUM
3. LABEL BREAKERS
4. GROUNDING ELECTRODE CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119
5. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES LABEL.
6. INSTALL ALL STRANDS UNDER TERMINAL LUG
7. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS.
8. PLEASE VERIFY PERMIT FOR NEW A/C UNIT
9. REDUCING WASHERS INSTALLED BACKWARDS.