Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE BOND A ROUND PLUMBING UNION TO MAINTAIN CONTINUITY. 2. RISE HARDWARE TO BE 1/4" MINIMUM 3. LABEL BREAKERS 4. GROUNDING ELECTRODE CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119 5. SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND INSTALL PER MANUFACTURES LABEL. 6. INSTALL ALL STRANDS UNDER TERMINAL LUG 7. ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINUM CONDUCTORS. 8. PLEASE VERIFY PERMIT FOR NEW A/C UNIT 9. REDUCING WASHERS INSTALLED BACKWARDS. |