Permit: T07CM04232
Permit Details
Status:
Final
Type:
SINGLE FAMILY ALTERATION
Address:
3338 N TUCSON BL #B
Address NEW:
3338 N TUCSON BL #B
Apply Date:
10/31/2007
Applicant:
SUNPOWER OF ARIZONA
Description:
SOLAR PANELS R1 Change panel connections Note H
Contractors:
- SUNPOWER OF ARIZONA
Outstanding Activity Conditions
Permit Number - T07CM04232
Permit Status: Final
Permit Description: SOLAR PANELS
R1 Change panel connections Note H
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/31/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07CM04232
Permit Description: SOLAR PANELS
R1 Change panel connections Note H
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | FRAMING | WLAHR | Approved | IVRS - Inspection :* PLANS OK |
| 12/27/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE EMT WITHIN 36" OF J-BOX 2) #10 STRANDED (OR ANY STRANDED CONDUCTOR) NOT ALLOWED UNDER GROUND SCREWS IN J-BOXES 3) SAME #10 TO BE USED TO GROUND SOLAR PANELS. NOT EMT AND CLIPS 4) NEED #8 TO SERVICE FOR GROUNDING ELECTRODE CONNECTION (PER PLAN) NOT NEW GROUND RODS NEC CALLS FOR DISCONNECTS TO BE GROUNDED/WE ARE IN DISCUSSION ABOUT THIS. OK FOR NOW, OK NO HOLDOWN ON INTER ACTIVE SYSTEM |
| 02/04/2008 | BUILDING - FINAL | DWALKER | Approved | IVRS - Inspection :* |
| 02/05/2008 | PERMIT FINALED | JWEATHER | Approved |