Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE EMT WITHIN 36" OF J-BOX
2) #10 STRANDED (OR ANY STRANDED CONDUCTOR) NOT ALLOWED UNDER GROUND SCREWS IN J-BOXES
3) SAME #10 TO BE USED TO GROUND SOLAR PANELS. NOT EMT AND CLIPS
4) NEED #8 TO SERVICE FOR GROUNDING ELECTRODE CONNECTION (PER PLAN) NOT NEW GROUND RODS NEC CALLS FOR DISCONNECTS TO BE GROUNDED/WE ARE IN DISCUSSION ABOUT THIS. OK FOR NOW, OK NO HOLDOWN ON INTER ACTIVE SYSTEM
12/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOFTOP
1. PANELS TO BE INDIVIDUALLY GROUNDED TO EQUIPMENT GROUND (#10) - NEC 110.3 B
2. GROUND J-BOXES - NEC 250
3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES AND CONDUIT BODIES - NEC 358.30
4. SECURE EMT TO ROOFTOP (ANCHOR ALL STRUT) -
NEC 110.13

ON GROUND
1. PROVIDE GROUNDING ELECTRODE FOR SYSTEM - NEC 690.47
2. SYSTEM DISCONNECT TO BE "GROUPED" WITH SERVICE DISCONNECT - NEC 690.14 A5
3. SEAL UNUSED OPENING IN INVERTER - NEC 110.12A
4. NEED HOLD DOWN KIT FOR BACKFED BREAKER -
NEC 408.36F
5. 2 #10 STRANDED NOT TO BE UNDER SAME TERMINATION IN INVERTER GROUND - NEC 110.3B

CHECK PLANS - INSTALLATION TO BE PER PLAN