Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE EMT WITHIN 36" OF J-BOX 2) #10 STRANDED (OR ANY STRANDED CONDUCTOR) NOT ALLOWED UNDER GROUND SCREWS IN J-BOXES 3) SAME #10 TO BE USED TO GROUND SOLAR PANELS. NOT EMT AND CLIPS 4) NEED #8 TO SERVICE FOR GROUNDING ELECTRODE CONNECTION (PER PLAN) NOT NEW GROUND RODS NEC CALLS FOR DISCONNECTS TO BE GROUNDED/WE ARE IN DISCUSSION ABOUT THIS. OK FOR NOW, OK NO HOLDOWN ON INTER ACTIVE SYSTEM |
|
| 12/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOFTOP 1. PANELS TO BE INDIVIDUALLY GROUNDED TO EQUIPMENT GROUND (#10) - NEC 110.3 B 2. GROUND J-BOXES - NEC 250 3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES AND CONDUIT BODIES - NEC 358.30 4. SECURE EMT TO ROOFTOP (ANCHOR ALL STRUT) - NEC 110.13 ON GROUND 1. PROVIDE GROUNDING ELECTRODE FOR SYSTEM - NEC 690.47 2. SYSTEM DISCONNECT TO BE "GROUPED" WITH SERVICE DISCONNECT - NEC 690.14 A5 3. SEAL UNUSED OPENING IN INVERTER - NEC 110.12A 4. NEED HOLD DOWN KIT FOR BACKFED BREAKER - NEC 408.36F 5. 2 #10 STRANDED NOT TO BE UNDER SAME TERMINATION IN INVERTER GROUND - NEC 110.3B CHECK PLANS - INSTALLATION TO BE PER PLAN |