Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
7927 N OLDFATHER DR
Apply Date:
10/03/2007
Applicant:
MARCY HOLLER
Description:
EXISTING WELL SITE TO BE MODERNIZED
Contractors:
  • GILBERT PUMP AND EQUIPMENT CO ,

Permit Reviews

Permit Number - T07CM03951
Permit Status: Expired
Permit Description: EXISTING WELL SITE TO BE MODERNIZED
Start Date Submittal Complete Date Status  
10/03/2007 PLANS OK TO SUBMIT - COMM 10/03/2007 COMPLETED Review Details
10/03/2007 COMMERCIAL NEW 11/20/2007 COMPLETED Review Details
11/20/2007 RESUBMITTAL 01/22/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM03951
Permit Status: Expired
Permit Description: EXISTING WELL SITE TO BE MODERNIZED
Total Outstanding Activity Conditions - 1
Date Name
10/03/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07CM03951
Permite Description: EXISTING WELL SITE TO BE MODERNIZED
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
BUILDING - FINAL N/A Not Inspected
01/17/2008 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
OK COVER, REMAINDER OF BRANCH CKT/L.V RACEWAYS
02/21/2008 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
RECALL FOR FINAL AFTER COMPLETION OF
EYE/WASH SHOWER
04/07/2008 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DISCONNECT FOR REMOVE COMPRESSOR MOTOR
NEC 430.102B
2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B
3. STRAP SEAL TIGHT FLEX - NEC 350.30
4. IDENTIFY ALL DISCONNECTS - NEC 110.22

IN FUTURE, BRANCH CKT'S AND FEEDERS ARE NOT TO BE ENERGIZED WITHOUT APPROVAL. EQUIPMENT IS TO BE OPEN/ACCESSIBLE AT TIME OF INSPECTION.

Completed Inspections

Permit Status: Expired
Permit Number: T07CM03951
Permit Description: EXISTING WELL SITE TO BE MODERNIZED
Total Completed Inspections - 6
Date Description Inspector Results Comments
12/31/2007 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection :*
1. PREVENT OBJECTIONABLE CURRENT - 250.6
2. SIZE NEUTRAL PER 220.61 (C)
3. MYERS HUBS TO BE LISTED FOR GROUNDING 110.3, 250.92

OK 4 GROUND RODS & CADWELDS
02/21/2008 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
INSTALL OF SAMPLE LINE AND 1 1/2 TO PRESSURE REDUCER BOX LOCATION FOR EYE WASH SHOWER OK
03/03/2008 ELECTRIC - TEMPORARY SERVICE CCLEMENS Approved IVRS - Inspection :*
03/03/2008 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
03/03/2008 ELECTRIC - SERVICE RELOCATION CCLEMENS Approved IVRS - Inspection :*
03/04/2008 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER C. CLEMENS

Documents

File Name Document Type  
T07CM03951_001.TIF CONSTRPLANS VIEW
T07CM03951_002.TIF CONSTRPLANS VIEW
T07CM03951_003.TIF CONSTRPLANS VIEW
T07CM03951_004.TIF CONSTRPLANS VIEW
T07CM03951_005.TIF CONSTRPLANS VIEW
T07CM03951_006.TIF CONSTRPLANS VIEW
T07CM03951_007.TIF CONSTRPLANS VIEW
T07CM03951_008.TIF CONSTRPLANS VIEW
T07CM03951_009.TIF CONSTRPLANS VIEW
T07CM03951_010.TIF CONSTRPLANS VIEW
T07CM03951_011.TIF CONSTRPLANS VIEW
T07CM03951_012.TIF CONSTRPLANS VIEW
T07CM03951_013.TIF CONSTRPLANS VIEW
T07CM03951_014.TIF CONSTRPLANS VIEW
T07CM03951_015.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW