Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE DISCONNECT FOR REMOVE COMPRESSOR MOTOR NEC 430.102B 2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B 3. STRAP SEAL TIGHT FLEX - NEC 350.30 4. IDENTIFY ALL DISCONNECTS - NEC 110.22 IN FUTURE, BRANCH CKT'S AND FEEDERS ARE NOT TO BE ENERGIZED WITHOUT APPROVAL. EQUIPMENT IS TO BE OPEN/ACCESSIBLE AT TIME OF INSPECTION. |
|
| 03/25/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR TO BE ON SITE TO OPEN EQUIPMENT LEAVE CONTACT PHONE NUMBER WHEN YOU CALL IN |