Permit: T07CM03951

Parcel: 22536003F


Addresses:

7927 N OLDFATHER DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DISCONNECT FOR REMOVE COMPRESSOR MOTOR
NEC 430.102B
2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B
3. STRAP SEAL TIGHT FLEX - NEC 350.30
4. IDENTIFY ALL DISCONNECTS - NEC 110.22

IN FUTURE, BRANCH CKT'S AND FEEDERS ARE NOT TO BE ENERGIZED WITHOUT APPROVAL. EQUIPMENT IS TO BE OPEN/ACCESSIBLE AT TIME OF INSPECTION.
03/25/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR TO BE ON SITE TO OPEN EQUIPMENT LEAVE CONTACT PHONE NUMBER WHEN YOU CALL IN