Permit: T07CM02824
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
10701 E MARY ANN CLEVELAND WY 02
Address NEW:
10701 E MARY ANN CLEVELAND WY 02
Apply Date:
07/02/2007
Applicant:
RELIABLE PERMIT MANAGEMENT
Description:
FOUNDATION ONLY
Architects:
- SWAIM, PHILLIP ELLIOTT
Contractors:
- LLOYD CONSTRUCTION COMPANY INC ,
Permit Reviews
Permit Number - T07CM02824
Permit Status: Final
Permit Description: FOUNDATION ONLY
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/02/2007 | PLANS OK TO SUBMIT - 3RD PARTY | 07/03/2007 | COMPLETED |
| 07/03/2007 | 3RD PARTY REVIEW-COMMERCIAL TI | 07/11/2007 | COMPLETED |
| 07/11/2007 | POST 3RD PARTY REVIEW | 07/16/2007 | COMPLETED |
| 07/16/2007 | RESUBMITTAL | 07/23/2007 | COMPLETED |
| 08/13/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 08/23/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM02824
Permit Status: Final
Permit Description: FOUNDATION ONLY
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/02/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07CM02824
Permit Description: FOUNDATION ONLY
Total Completed Inspections - 14
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2007 | ELECTRIC - UFER | RJIROUDE | Approved | IVRS - Inspection :* 1. OK #6 TO REBAR IN FOOTING FOR TELEPHONE BOARD 2. OK 3/0 TO REBAR IN FOOTING FOR NEW SWITCHBOARD DS AND H 3. OK #2 TO REBAR IN FOOTING FOR 75KVA XFMR 4. OK 2/0 TO REBAR IN FOOTING FOR 500KVA XFMR |
| 09/25/2007 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | IVRS - Inspection :* CMU WALL FOOTING @ THE WEST SIDE GRID LINES A/2 TO 4 W/DOOR OPENING |
| 10/03/2007 | STEM WALL/RETAINING WALL | GDABBS | Approved | IVRS - Inspection :* MASONRY REINFORCEMENT STEEL @ GRID LINES A/2 TO 4 B/2.5 TO 6 - 6/B TO F & G TO J - 6 FROM F-G FOOTING LINE J FROM 3.5 |
| 10/04/2007 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* PRE-SLAB ROOMS 103, 105, 107, 109 OK T07CM01713 SHALL CONTINUE INSPECTIONS ON THIS SITE |
| 10/04/2007 | BUILDING PRE-SLAB | GDABBS | Approved | IVRS - Inspection :* |
| 10/04/2007 | PLUMBING - PRE SLAB | RRICH | Approved | IVRS - Inspection :* |
| 10/04/2007 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :* |
| 10/04/2007 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 10/08/2007 | ELECTRIC - UNDERGROUND | RJIROUDE | Approved | IVRS - Inspection :* 1. OK 3 - 3" PVC TO DIMMER BANK SLDB 2. OK 1 - 1 1/4" PVC TO BP 3. OK RIGID CONDUITS AT CONNECTION FROM EAST & WEST TRENCH TO CONNECTION TO A/V JUNCTION BOX |
| 09/04/2008 | BUILDING - FINAL | GDABBS | Approved | |
| 09/04/2008 | REINFORCED MASONRY PRE-GROUT | GDABBS | Approved | |
| 09/04/2008 | FIRE - FINAL | LTHOMAS | Approved | |
| 09/04/2008 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 03/04/2009 | PERMIT FINALED | LJACKSON | Approved |