Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Apply Date:
12/17/2007
Applicant:
S & M FIRE SYSTEMS INC/IDEAL FIRE **C**
Description:
KITCHEN HOOD SYSTEM
Contractors:
  • S & M/ IDEAL FIRE CONTROL INC *C

Permit Reviews

Permit Number - T07BU02604
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Start Date Submittal Complete Date Status  
12/17/2007 MECHANICAL 12/18/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07BU02604
Permit Status: Expired
Permit Description: KITCHEN HOOD SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
12/17/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07BU02604
Permite Description: KITCHEN HOOD SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
01/02/2008 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
THE HOOD & GREASE DUCT UP TO ROOF ARE OK TO USE.
HOWEVER, THE BLOWER & RELATED DUCT WORK IS NOT APPROVED FOR TYPE I THE BLOWER IS A UTILITY BLOWER AND IS NOT INTERLOCKED WITH ANY MAKE UP AIR. ALSO, EXHAUST BLOWER MUST HAVE A DISCONNECTING MEANS ON THE ROOF. THE NEW BLOWER & MAKE UP AIR MUST BE AN ENGINEERED SYSTEM APPROVED BY CITY OF TUCSON.

Documents

File Name Document Type  
HOOD_001.TIF FIRE PLANS VIEW
HOOD_002.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW