Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T07BU02604

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/02/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
THE HOOD & GREASE DUCT UP TO ROOF ARE OK TO USE.
HOWEVER, THE BLOWER & RELATED DUCT WORK IS NOT APPROVED FOR TYPE I THE BLOWER IS A UTILITY BLOWER AND IS NOT INTERLOCKED WITH ANY MAKE UP AIR. ALSO, EXHAUST BLOWER MUST HAVE A DISCONNECTING MEANS ON THE ROOF. THE NEW BLOWER & MAKE UP AIR MUST BE AN ENGINEERED SYSTEM APPROVED BY CITY OF TUCSON.