Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU02604
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* THE HOOD & GREASE DUCT UP TO ROOF ARE OK TO USE. HOWEVER, THE BLOWER & RELATED DUCT WORK IS NOT APPROVED FOR TYPE I THE BLOWER IS A UTILITY BLOWER AND IS NOT INTERLOCKED WITH ANY MAKE UP AIR. ALSO, EXHAUST BLOWER MUST HAVE A DISCONNECTING MEANS ON THE ROOF. THE NEW BLOWER & MAKE UP AIR MUST BE AN ENGINEERED SYSTEM APPROVED BY CITY OF TUCSON. |