Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07BU00586
Permit Details
Apply Date:
03/16/2007
Applicant:
ROADRUNNER FIRE AND SAFETY EQUIP
Description:
KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Contractors:
- ROADRUNNER FIRE AND SAFETY EQUIP
- ROADRUNNER FIRE* C
Permit Reviews
Permit Number - T07BU00586
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/16/2007 | MECHANICAL | 03/16/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07BU00586
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
03/16/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07BU00586
Permite Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOOD APPEARS TO BE TYPE 1 THE DUCT CONNECTIONS TO THE HOOD ARE SEALED WITH CAULKING - NEEDS TO BE WELDED THE FANS ON THE ROOF ARE NOT TYPE 1 & THE DUCT ON ROOF IS NOT WELDED TO THE GREASE DUCT RISER. GAS PIPE DOES NOT APPEAR TO BE SIZED CORRECTLY PROVIDE A MECHANICAL PERMIT, AN APPROVED SET OF DRAWINGS WITH AN ENGINEERED EXHAUST SYSTEM AND A TOTAL BTU DEMAND ON ALL COOKING APPLIANCES |
Completed Inspections
Permit Status: Expired
Permit Number: T07BU00586
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2007 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | GAS NOT SHUTTING OFF |