Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T07BU00586
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOOD APPEARS TO BE TYPE 1 THE DUCT CONNECTIONS TO THE HOOD ARE SEALED WITH CAULKING - NEEDS TO BE WELDED THE FANS ON THE ROOF ARE NOT TYPE 1 & THE DUCT ON ROOF IS NOT WELDED TO THE GREASE DUCT RISER. GAS PIPE DOES NOT APPEAR TO BE SIZED CORRECTLY PROVIDE A MECHANICAL PERMIT, AN APPROVED SET OF DRAWINGS WITH AN ENGINEERED EXHAUST SYSTEM AND A TOTAL BTU DEMAND ON ALL COOKING APPLIANCES |