Description:
REPLACE:GASLINE
Permit Reviews
Permit Number - T06PL02382
Permit Status: Final
Permit Description: REPLACE:GASLINE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/21/2006 | PLUMBING | 12/21/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06PL02382
Permit Status: Final
Permit Description: REPLACE:GASLINE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/21/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06PL02382
Permit Description: REPLACE:GASLINE
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2006 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) I'M SORRY I DIDN'T GET YOUR MESSAGE YESTERDAY; I WAS HAVING PHONE PROBLEMS AND DIDN'T HEAR IT UNTIL THIS MORNING 2) GAS PIPE REQUIRES A MINIMUM OF 12" OF COVER AT ALL POINTS 3) FIELD WRAPPING IS REQUIRED WHERE PIPING HAS BEEN STRIPPED FOR THREADING OR MARRED BY WRNCHES, ALL WRENCH MARKS ARE TO BE TAPED 4) ALL FIXED APPIANCES ARE TO HAVE A SEDIMENT TRAP 5) PROVIDE INSPECTION HISTORY FOR NEW FARNESS 6) T & P RELIEF DRAIN TO BE GRAVITY TYPE 7) BOND REQUIRED BETWEEN GAS AND METALLIC WATER PIPING |
| 12/29/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 01/09/2007 | PERMIT FINALED | BFLORES | Approved |