Permit: T06PL02382

Parcel: 106063370


Addresses:

3660 N TUTTLE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/08/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04090 -- APPROVED PERMIT #T07ME00006
NOTE: PERMANENT CAP OLD GAS PIPING IN FURNACE CLOSET
12/29/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) I'M SORRY I DIDN'T GET YOUR MESSAGE YESTERDAY; I WAS HAVING PHONE PROBLEMS AND DIDN'T HEAR IT UNTIL THIS MORNING
2) GAS PIPE REQUIRES A MINIMUM OF 12" OF COVER AT ALL POINTS
3) FIELD WRAPPING IS REQUIRED WHERE PIPING HAS BEEN STRIPPED FOR THREADING OR MARRED BY WRNCHES, ALL WRENCH MARKS ARE TO BE TAPED
4) ALL FIXED APPIANCES ARE TO HAVE A SEDIMENT TRAP
5) PROVIDE INSPECTION HISTORY FOR NEW FARNESS
6) T & P RELIEF DRAIN TO BE GRAVITY TYPE
7) BOND REQUIRED BETWEEN GAS AND METALLIC WATER PIPING
12/28/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NOBODY HOME