Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3762 E 23RD ST
Address NEW:
3762 E 23RD ST
Apply Date:
11/17/2006
Applicant:
ARMANDO MARQUEZ
Description:
NEW:GAS LINE

Permit Reviews

Permit Number - T06PL02130
Permit Status: Expired
Permit Description: NEW:GAS LINE
Start Date Submittal Complete Date Status  
11/17/2006 PLUMBING 11/17/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06PL02130
Permit Status: Expired
Permit Description: NEW:GAS LINE
Total Outstanding Activity Conditions - 1
Date Name
11/17/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06PL02130
Permite Description: NEW:GAS LINE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
11/24/2006 PLUMBING - GAS PRESSURE TEST N/A Partial Approval IVRS - Inspection :*
14 PSI TEST FROM METER UNDERGROUND
UP AT BUILDING OVERHEAD TO STOVE, WATER HEATER, FURNACE. PARTIAL APPROVAL STOVE STUB IS 30" AFF IF CHANGE IS MADE RETEST.
1. PROVIDE PERMITS FOR NEW WATER HEATER & FURNACE.
11/24/2006 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL PIPING PENETRATION INTO BUILDING.
2. PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH CORRECT INSTALLATION FOR WATER HEATER TEMPERATURE AND PRESSURE RELIEF (ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF).
3. BONDING OF BUILDING GAS PIPING TO BE TO BUILDING COLD WATER PIPING.
4. VENT FROM WATER HEATER TO BE DOUBLE WALL THRU CEILING & ROOF WITH 1" MINIMUM CLEARANCE FROM COMBUSTIBLES FOR DOUBLE WALL VENT PIPING TERMINATING WITH APPROVED VENT CAP MINIMUM OF 2' ABOVE ANY AIR INTAKES.
6. VENT FROM FURNACE TO HAVE 1" MINIMUM CLEARACE FROM COMBUSTIBLES. NOTE: ALL VENT CONNECTIONS TO BE MADE UP CORRECTLY. PROVIDE CORRECT COMBUSTION AIR FOR FURNACE.