Permit: T06PL02130

Parcel: 130070620


Addresses:

3762 E 23RD ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/24/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL PIPING PENETRATION INTO BUILDING.
2. PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH CORRECT INSTALLATION FOR WATER HEATER TEMPERATURE AND PRESSURE RELIEF (ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF).
3. BONDING OF BUILDING GAS PIPING TO BE TO BUILDING COLD WATER PIPING.
4. VENT FROM WATER HEATER TO BE DOUBLE WALL THRU CEILING & ROOF WITH 1" MINIMUM CLEARANCE FROM COMBUSTIBLES FOR DOUBLE WALL VENT PIPING TERMINATING WITH APPROVED VENT CAP MINIMUM OF 2' ABOVE ANY AIR INTAKES.
6. VENT FROM FURNACE TO HAVE 1" MINIMUM CLEARACE FROM COMBUSTIBLES. NOTE: ALL VENT CONNECTIONS TO BE MADE UP CORRECTLY. PROVIDE CORRECT COMBUSTION AIR FOR FURNACE.