Permit Details

Status:
Final
Type:
SIGN PERMIT
Address:
3921 E PIMA ST
Apply Date:
12/08/2006
Applicant:
SPENCER SIGNS *C
Description:
12323
Contractors:
  • SPENCER SIGNS *C

Completed Inspections

Permit Status: Final
Permit Number: T06OT03184
Permit Description: 12323
Total Completed Inspections - 5
Date Description Inspector Results Comments
12/15/2006 SIGN SITE REVIEW JYBARRA Approved
12/21/2006 SIGN SHOP RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN GTO CLEARANCE 1 1/2" FROM GROUNDED SURFACES SPAGHETTI GLASS NON-EFFECTIVE
2. USE CORRECT SIZED BOOT FOR GTO CABLE DO NOT CUT SLEEVING.
3. CANNOT USE 600 V TERMINAL END ON 15,000V CABLE
4. ONLY ONE CONDUCTOR TO A TERMINAL CONNECTION.
02/05/2007 SIGN INSPECTION JYBARRA Approved IVRS - Inspection :*
02/07/2007 SIGN ELECTRIC RHOLLAND Approved IVRS - Inspection :*
02/08/2007 PERMIT FINALED JWEATHER Approved