Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T06OT03184
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
02/06/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
01/10/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK SHOP 1. CHECK POWER ON SITE 2. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
12/21/2006 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN GTO CLEARANCE 1 1/2" FROM GROUNDED SURFACES SPAGHETTI GLASS NON-EFFECTIVE 2. USE CORRECT SIZED BOOT FOR GTO CABLE DO NOT CUT SLEEVING. 3. CANNOT USE 600 V TERMINAL END ON 15,000V CABLE 4. ONLY ONE CONDUCTOR TO A TERMINAL CONNECTION. |