Outstanding Inspections

Permit Status: Expired
Permit Number: T06OT03000
Permite Description: 12194
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
07/31/2008 SIGN SHOP N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. UNTIE SHIPPING KNOTS IN GTO CABLES
2. TAKE UP SLACK GTO IN TRANSFORMER ENCLOSURE
3. PROPERLY GROUND ENCLOSURE
4. SIGN TO BE SWITCHED PER 600.6
5. CHECK REAR SIGN NEXT TIME
6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR
7. A SERVICE LIGHT IS NEEDED
07/31/2008 SIGN ELECTRIC N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*

Completed Inspections

Permit Status: Expired
Permit Number: T06OT03000
Permit Description: 12194
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/20/2006 SIGN SITE REVIEW JSONKIN Approved IVRS - Inspection :*
06/20/2007 SIGN INSPECTION JSONKIN Approved IVRS - Inspection :*